無菌室一般是在生物實驗室內專辟的一個小房間,面積不宜過大,約4m2~5m2,高2.5m左右即可。此外提醒您,
無菌室裝修時的門窗不要忘記多關注!
The sterile room is generally a small room specially built in the biological laboratory, and the area should not be too large, about 4m2~5m2, and about 2.5m high. In addition, please don't forget to pay more attention to the doors and windows when decorating the sterile room!
(1)無菌室、準備室、儀器室門為彩鋼板門板、鋁合金包邊,鋁合金門框為厚度1.2mm,門板包邊鋁合金厚度1.0mm,并在門上方開觀察窗,窗體采用專用的噴塑鋁合金型材,并采用圓弧過濾。彩鋼板。
(1) The doors of sterile room, preparation room and instrument room are made of color steel plate door panels and aluminum alloy edging, the thickness of aluminum alloy door frame is 1.2 mm, the thickness of aluminum alloy edging is 1.0 mm, and the observation window is opened above the door. The window is made of special plastic-sprayed aluminum alloy profiles and filtered by circular arc. Color steel plate.
(2)無菌室彩鋼板上觀察窗為雙層密閉窗,窗體采用專用的噴塑鋁合金型材,并采用圓弧過度。
(2) The observation window on the color steel plate of the sterile room is a double-layer airtight window, and the window is made of special plastic-sprayed aluminum alloy profile, with arc transition.
(3)吊掛件、錨固件應做防腐、防銹處理。
(3) Hangers and anchors shall be subject to anti-corrosion and anti-rust treatment.
(4)金屬夾心板施工安裝前應嚴格畫線、編號。墻角應垂直交接。
(4) Before the construction and installation of metal sandwich panels, the lines and numbers shall be strictly drawn. The wall corners shall be connected vertically.

(5)安裝過程中不得剝離金屬夾心板表面保護膜,不得撞擊板面(6)各類墻面表面平整度允許偏差為2mm,立面垂直度允許偏差為2mm,陰陽角弧度允許偏差為2度。
(5) During installation, the protective film on the surface of the metal sandwich plate shall not be peeled off, and the plate surface shall not be hit. (6) The allowable deviation of the flatness of various wall surfaces shall be 2mm, the allowable deviation of the verticality of the facade shall be 2mm, and the allowable deviation of the internal and external angle radian shall be 2 degrees.
(7)正壓潔凈室應在金屬夾心板正壓面用中性密封膠密封縫隙。當負壓潔凈室不能在負壓面密封時,應在縫內嵌密封條擠緊,并應在室內面涂密封膠密封。
(7) The positive pressure clean room shall seal the gap with neutral sealant on the positive pressure surface of the metal sandwich panel. When the negative pressure cleaning room cannot be sealed on the negative pressure surface, the sealing strip shall be embedded in the joint to squeeze tightly, and the indoor surface shall be sealed with sealant.
(8)金屬夾心板墻面的金屬面與骨架之間應有導靜電措施。
(8) Electrostatic conductive measures shall be taken between the metal surface of the metal sandwich panel wall and the framework.
In the air of general environment, due to the existence of many dust and miscellaneous bacteria, it is easy to cause pollution and greatly interfere with the vaccination work, so be more careful when using the sterile room, and more relevant content can be found on our website http://www.tangmarts.com Consult!